Controller and Display

CHS Series

12

2.4.1.2 CH Config - Outdoor Reset Config

Figure 2-10 Outdoor Reset Configuration Screen

(CH Config) Outdoor Reset Config – sub-menu
screen, allows the installer to set parameters specific
to the effect the outdoor temperature has on the
operation of the boiler during local (i.e. non Lead
Lag) Central Heat demands. Use the up and down
(▲▼) buttons to navigate the menu options; when
the desired option is highlighted select by pressing the
“OK” button.

Outdoor Reset is in effect only if the following two
conditions are met: “Outdoor reset” is set to "Enable",
and an outdoor temperature sensor is connected to the
boiler. The “Outdoor Reset Config” parameters,
together with the “CH Config” parameters, define the
relationship of boiler temperature setpoint to outdoor
temperature. Refer to Figure 2-12 for an example of
the relationship between outdoor temperature and
boiler temperature, with a given set of settings.

Table 2-7 Outdoor Reset Configuration Parameters

Parameter

Description

Factory Settings

Outdoor reset
enable

Enables or disables Outdoor reset

Enabled

Max outdoor
temp

Outdoor temperature that corresponds to the “Low water temp” setting. Example:

If the “Low water temp” setting is 95°F, and the “Max outdoor temp” setting is
70°F, the boiler setpoint will be 95°F when the outdoor temperature is 70°F or
higher. Range 50°F to 95°F

70ºF

Min outdoor
temp

Design Temperature - Outdoor temperature that corresponds to the “CH

setpoint” setting. Example: If the “CH setpoint” is 180°F, and the “Min outdoor

temp” setting is 0°F, the boiler setpoint will be 180°F when the outdoor
temperature is 0°F or lower. Range -40°F to 40°F

0ºF

Low water temp

Minimum boiler setpoint; occurs when the outdoor temperature is equal to or

greater than the “Max outdoor temp”. Range 60°F to 140°F

95ºF

Outdoor boost
max off point

Read only – functional in future revisions.

130ºF

Figure 2-11 Outdoor Reset Graph

Outdoor

reset

Max

outdoor

temp

Min

outdoor

temp

Low

water

temp

Outdoor

boost

max

off

point

Enable

70

o

F

0

o

F

95

o

F

130

o

F

Outdoor

Reset

Config

Point defined by:
Min outdoor temp= 0ºF

Point defined by:
Max outdoor temp= 70ºF