Slant fin corp, Pump, Config – Slant/Fin CHS-399 User Manual

Page 24: Controller and display chs series

Advertising
background image

Slant Fin Corp.

Controller and Display

CHS Series

22

2.4.4.2 Pump Config

Figure 2-20 Pump Configuration

Pump Config – sub-menu screen allows adjustment
of the individual pump overrun times; also allows the
individual pumps to be manually turned on for testing
purposes. Use the up and down (▲▼) buttons to
navigate the menu options; when the desired option is
highlighted select by pressing the “OK” button.

CH pump use for LL Master – for Lead Lag
multiple boiler configurations; set this parameter to
“On” on the boiler that is controlling the System
pump with the Pump C output.

pump control – This may be
used to manually override

automatic control of the pumps for testing purposes.
If used in this manner, ensure that it is set back to
“Auto”; otherwise, the selected pump(s) will remain
powered on indefinitely.

Table 2-14 Pump Configuration Parameters

Parameter

Description

Factory Settings

CH pump
control *

Switches CH pump (Pump C) control from Automatic to ON.

Auto

CH overrun
time *

Amount of time the CH pump (Pump C) will continue to run after a CH [CH1
or CH2 (LL)] demand ends. Range 0 to 1080 minutes.

0 sec

CH pump use for
LL master *

Check box used to allocate Pump C output as the system pump operator for
Lead Lag applications.

off

Boiler pump
control *

Switches Boiler pump (Pump B) control from Automatic to ON.

Auto

Boiler pump
overrun time *

Amount of time the Boiler pump (Pump B) will continue to run after burner
shutdown. Range 0 to 1080 minutes.

30 sec

DHW pump
control *

Switches DHW pump (Pump A) control from Automatic to ON.

Auto

DHW pump
overrun time *

Amount of time the DHW pump (Pump A) will continue to run after a DHW
demand ends. Range 0 to 1080 minutes.

10 sec

* = Password protected

CH

pump

control

CH

pump

overrun time

CH

pump

use

for

LL

Master

Boiler

pump

control

Boiler

pump

overrun

time

DHW pump

control

DHW pump overrun time

Auto

0 sec

off

Auto

30 sec

Auto

10 sec

Pump

Config

Advertising
This manual is related to the following products: