2.4.5 Modulation Config

Figure 2-24 Modulation Configuration Screen

Modulation Config – menu screen, accessed by
selecting “Modulation Config” from the “Advanced
Setup” screen, allows for adjustment of the min. and
max. modulation rates of the boiler. Use the up and
down (▲▼) buttons to navigate the menu options;
when the desired option is highlighted select by
pressing the “OK” button.

Modulation rates are listed by model number:

CH and DWH

Max Modulation Rate

Min Modulation

Rate

CHS-85 = 6300
CHS-110 = 7000
CHS-155 = 3700
CHS-175 = 4100
CHS-200 = 4650
CHS-250 = 5900
CHS-300 = 5000 (4800 on LP)
CHS-399 = 6900 (6600 on LP)

85

= 1525

110 = 1625
155 = 900
175 = 900
200 = 900
250 = 900
300 = 1500
399 = 1500

Table 2-18 Modulation Configuration Parameters

Parameter

Description

Factory Settings

CH max
modulation rate *

Maximum permissible blower speed during CH demand [CH1 or CH2 (LL)].
Range is model dependent.

Model dependent

DHW max
modulation rate *

Maximum permissible blower speed during DHW demand. Range is model
dependent.

Model dependent

Min modulation
rate *

Minimum permissible blower speed. Range is model dependent.

Model dependent

* = Password protected

CH

max

modulation

rate

DHW

max

modulation

rate

Min

modulation

rate

7000 RPM

7000 RPM

1625 RPM

Modulation Config