2.4.6 Delta T & T-rise Limits
Delta T Limits
– accessed by selecting “Delta T Limits” from the “Advanced Setup” screen; Delta T is the
difference in water temperature between Inlet and Outlet of the boiler. If the temperature difference (Delta T) is
greater than 60

o

F the burner is shut off for the time specified before firing again. An initial cycle and two recycles

are allowed before Lockout occurs.

T-rise Limits – accessed by selecting “T-rise Limits” from the “Advanced Setup” screen; T-rise is the rate of
increase of the boiler Outlet temperature. If the boiler outlet temperature increases by a rate greater than
4

o

F/second the burner will recycle with a delay equal to the “Outlet T-rise delay” setting. An initial cycle and two

recycles are allowed before Lockout occurs.

Figure 2-25 Delta T & T-rise Limits Screens

Table 2-19 Delta T & T-rise Limits Parameters

Parameter

Description

Factory Settings

Delta T
delay *

Delay time between burner cycles when Delta T limit is exceeded. Range 1 to 60
minutes.

5 min

Outlet T-rise
delay *

Delay time between burner cycles when T-rise limit is exceeded. Range 1 to 60
minutes.

5 min

*=Password Protected



















Outlet T-rise delay

5 min

T-rise Limits

Delta T delay

5 min

Delta T Limits