2.4.3.3 Lead Lag Outdoor Reset

Figure 2-17 LL Outdoor Reset Screen

(LL Config) Outdoor Reset Config – sub-menu
screen, allows the installer to set parameters specific
to the effect the outdoor temperature has on the
operation of the boiler during a CH2 (LL) demand.
Use the up and down (▲▼) buttons to navigate the
menu options; when the desired option is highlighted
select by pressing the “OK” button.

Outdoor Reset is in effect only if the following two
conditions are met: “Outdoor reset enable” is set to
"Enable", and an outdoor temperature sensor is
connected to the boiler. The “Lead Lag Outdoor
Reset” parameters, together with the “Lead Lag
Master Config” parameters, define the relationship of
boiler temperature setpoint to outdoor temperature.
Refer to Figure 2-12 for an example of the
relationship between outdoor temperature and boiler
temperature, with a given set of settings.


Table 2-12 Lead Lag Outdoor Reset Config Parameters

Parameter

Description

Factory Settings

Outdoor reset
enable *

Enables or disables Outdoor reset

Enabled

Max outdoor
temp *

Outdoor temperature that corresponds to the “Low water temp” setting. Example:

If the “Low water temp” setting is 85°F, and the “Max outdoor temp” setting is
70°F, the boiler setpoint will be 85°F when the outdoor temperature is 70°F or
higher. Range 50°F to 95°F

70ºF

Min outdoor
temp *

Design Temperature - Outdoor temperature that corresponds to the “Setpoint”
setting. Example: If the “Setpoint” is 150°F, and the “Min outdoor temp” setting
is 0°F, the boiler setpoint will be 150°F when the outdoor temperature is 0°F or
lower. Range -40°F to 40°F

0ºF

Low water
temp *

Minimum boiler setpoint; occurs when the outdoor temperature is equal to or

greater than the “Max outdoor temp”. Range 60°F to 140°F

85ºF

Outdoor boost
max off point *

Read only – functional in a future revision.

130ºF

* = Password protected

Outdoor

reset enable

Max

outdoor

temp

Min

outdoor

temp

Low

water

temp

Outdoor

boost

max

off

point

Enable

70

o

F

0

o

F

85

o

F

130

o

F

Lead

Lag

Outdoor

Reset