CHS Series

Controller and Display

Slant Fin Corp.

5

2.1

Quick Start

Figure 2-2 Quick Start Screen

Quick Start – screen, accessed by selecting
“Quick Start” from the “i-Information” screen,
provides a summary of the most common settings
that will need to be adjusted (or considered) when
initially setting up the boiler. Use the up and down
(▲▼) buttons to navigate the menu options; when
the desired option is highlighted select by pressing
the “OK” button.

Each of the parameters under Quick Start are also
listed under separate setting groups under
“Advanced Setup”; where more advanced settings
can be accessed..

Table 2-2 Quick Start Configuration Parameters

Parameter

Description

Factory Setting

CH setpoint

Setpoint value for CH modulation. If “Outdoor reset” is set to “Disable”, this is
the target temperature at the “Modulation sensor”. If “Outdoor reset” is set to

“Enable”, this is the maximum target temperature at the “Modulation sensor”
(Setpoint for CHI heat input).

180ºF

DHW setpoint

Boiler setpoint for DHW modulation. Range 60°F to 190°F

180ºF

Outdoor reset

Enables or disables CH outdoor reset function for CH1 heat inputs.

Enable

Low water temp

Minimum boiler setpoint; occurs when the outdoor temperature is equal to or

greater than the “Max outdoor temp”. Range 60°F to 140°F

95ºF

Max outdoor temp

Outdoor temperature that corresponds to the “Low water temp” setting.
Example: If the “Low water temp” setting is 95°F, and the “Max outdoor
temp” setting is 70°F, the boiler setpoint will be 95°F when the outdoor
temperature is 70°F or higher. Range 50°F to 95°F

70ºF

Min outdoor temp

Design Temperature - Outdoor temperature that corresponds to the “CH

setpoint” setting. Example: If the “CH setpoint” is 180°F, and the “Min

outdoor temp” setting is 0°F, the boiler setpoint will be 180°F when the
outdoor temperature is 0°F or lower. Range -40°F to 40°F

0ºF

Adjustable high
limit

Outlet water temperature high limit. Controller will not permit burner
operation above this setting. Recommend leaving configured as 200ºF. Range
100°F to 200°F

200ºF

Adjustable stack
limit

Stack exhaust gas high limit. Controller will lockout if exhaust gas
temperature exceeds this setting. Range 145°F to 220°F

220ºF



CH setpoint

DHW setpoint

Outdoor reset

Low water temp

Max outdoor temp

Min outdoor temp

Adjustable high limit

Adjustable stack limit

180

o

F

180

o

F

Enable

95

o

F

70

o

F

0

o

F

200

o

F

220

o

F