CHS Series

Controller and Display

Slant Fin Corp.

7

2.3.1 Forced Rate

Figure 2-5 Forced Rate Test Screen

Forced Rate – test screen, permits the installer to
force the burner to operate at “high fire” or “low fire”
for the purpose of combustion setup and diagnoses.
Set the “Manual firing rate” to high or low fire by
using the up and down (▲▼) buttons to highlight
either “Set high fire” or “Set low fire”; then select it
by pressing the “OK” button.

When the test is complete, select “Stop test” to return
firing rate control to automatic.


The burner MUST be firing
to initiate “Start test”.

Table 2-3 Forced Rate Parameters

Parameter

Description

Set high fire *

When selected, sets “Manual firing rate” setting equal to the maximum modulation rate of the boiler.

Set low fire *

When selected, sets “Manual firing rate” setting equal to the minimum modulation rate of the boiler.

Start test *

When selected, initiates the forced rate test, burner will operate at the “Manual firing rate” setting

indicated on the screen. To stop test select “Stop test”; which will be displayed in place of “Start test”
once the test is initiated.

* = Password protected

State

Firing rate

Fan speed

Outlet temp

Manual firing rate

Test State: Idle
Test Timer: 0 sec

Set high fire

Set low fire

Start test


Standby

0 RPM

Low

71

o

F

1625 RPM

Forced

Rate

Burner must be in run state