CHS Series

Controller and Display

Slant Fin Corp.

13

2.4.1.3 CH Config - Warm Weather Shutdown

Figure 2-12 WWSD Configuration Screen

(CH

Config)

Warm

Weather

Shutdown

(WWSD) – sub-menu screen, allows the installer to
enable the WWSD function for local (i.e. non Lead
Lag) Central Heat demands, and define at what
outdoor temperature it is initiated. Use the up and
down (▲▼) buttons to navigate the menu options;
when the desired option is highlighted select by
pressing the “OK” button.

When “Warm weather shutdown” is set to one of the
“Shutdown” options, and the outdoor temperature is
above the “Warm weather shdn setpoint”, CH
operation is inhibited.

CH operation is restored when the outdoor
temperature drops below the WWSD setpoint by a
fixed value of 4ºF.

Table 2-8 Warm Weather Shutdown Configuration Parameters

Parameter

Description

Factory Settings

Warm weather
shutdown

Enable or Disable Warm Weather Shutdown and select shutdown options

Shutdown after demand ends

Shutdown immediately

Disable

Disable

Warm weather
shdn setpoint

Temperature at which local Central Heat operation is inhibited. Not applicable

when “Warm weather shutdown” is set to “Disable”. Range 50°F to120°F

60°F

Warm

weather

shutdown

Warm

weather

shdn

setpoint

Disable

60

o

F

Warm

Weather

Shutdown