Slant fin corp, Frost, Protection – Slant/Fin CHS-399 User Manual

Page 30: Config

Advertising
background image

Slant Fin Corp.

Controller and Display

CHS Series

28

2.4.7 Frost Protection Config

Figure 2-26 Frost Protection Screen

Frost Protection Config – accessed by selecting
“Frost Protection Config” from the “Advanced
Setup” screen. Provides optional freeze protection
for the boiler system. Use the up and down (▲▼)
buttons to navigate the menu options; when the
desired option is highlighted select by pressing the
“OK” button.

When set to “Enable”, causes the respective
circulators to operate when the inlet temperature
drops below 45°F; and the burner to fire (at the min.
modulation rate) when the outlet temperature drops
below 38°F.

Table 2-20 Frost Protection Configuration Parameters

Parameter

Description

Factory Settings

CH frost
protection *

Enable or Disable frost protection for central heat (i.e. Pumps B and C).

Enabled

DHW frost
protection *

Enable or Disable frost protection for DHW (i.e. Pumps A and B).

Disabled

Lead Lag frost
protection *

Enable or Disable frost protection for lead lag (i.e. Pumps B and C). Each slave
detects frost protection and notifies the Master.

Disabled

* Password protected

CH frost protection

DHW frost protection

Lead Lag frost protection

Enable

Disable

Disable

Frost

Protection

Config