15

EM-40-SM Service Manual

Note:

DIP switches are located on the front of the control.

(A) Factory / Installer

The Factory / Installer DIP switch is used to select which
items are available to be viewed and / or adjusted in the
user interface. The Factory Access Level includes all
the settings available in the control. The Installer Access
Level includes the settings and items which are required
for system setup.

(B) Not Used

DIP Switch Settings

Control Settings

Applications

Mode 1 and 2 – Two Setpoint Operation

Mode 1 – Two Setpoint Operation with Parallel Piping

The control receives a heat demand provided from zone
valve end switches or a switching relay end switch. The
control turns on the boiler pump and operates the burners
to maintain the setpoint boiler target 1 temperature at the
boiler outlet sensor whenever a heat demand is present.
The control receives a setpoint demand from a DHW
aquastat. The control operates the burners to maintain the
setpoint boiler target 2 at the boiler outlet sensor whe
never a setpoint demand is present.

Note:

An external relay is required to operate the DHW

pump and provide DHW priority if required by disabling
the boiler pump.

Mode 2 – Two Setpoint Operation with Primary /
Secondary Piping

The control receives a heat demand provided from zone
valve end switches or a switching relay end switch. The
control turns on the boiler pump and operates the burners
to maintain the boiler target 1 temperature at the boiler
supply sensor whenever a heat demand is present. The
control receives a setpoint demand from a DHW aquastat.
The control operates the burners to maintain the setpoint
boiler target 2 at the boiler supply sensor whenever a
setpoint demand is present.

Note:

An external relay is required to operate the DHW

pump and provide DHW priority if required by disabling
the system pump.

Factory

Installer

OFF

OFF

B

A

BTC

Mode 1

Relay

Boiler Inlet Sensor (Included)

Factory

Installed

Boiler

Outlet

Sensor

BTC

Mode 2

Zone Box

Relay

Boiler Inlet Sensor (Optional)

Factory

Installed

Boiler

Outlet

Sensor

Secondary

Piping

Sensor

(Included)