EM-40-SM Service Manual

Mode 4 and 5 – Outdoor Reset and Setpoint Operation - View Menu

s

s

e

c

c

A

n

o

i

t

p

i

r

c

s

e

D

e

g

n

a

R

d

l

e

i

F

m

e

t

I

-60 to 190°F

(-51 to 88°C)

OUTDOOR

Current outdoor air temperature as measured by the
outdoor sensor.

Factory

Installer

- - - ,

35 to 266°F

(2 to 130°C),

OFF

BOILER TARGET

The boiler target is the temperature the control is
currently trying to maintain at the boiler supply sensor
or the boiler outlet sensor.

Factory

Installer

14 to 266°F

(-10 to 130°C)

BOILER SUPPLY

Current boiler supply water temperature as measured
by the boiler supply sensor.

Note: This item is only available when MODE is set to 5.

Factory

Installer

14 to 266°F

(-10 to 130°C)

BOILER OUTLET

Current boiler outlet water temperature as measured
by the boiler outlet sensor.

Note: When MODE is set to 5 this item is only visible
in the Factory access level.

Factory

(Installer for

Mode 4)

14 to 266°F

(-10 to 130°C)

BOILER INLET

Current boiler inlet water temperature as measured by
the boiler inlet sensor.

Note: This item is only available when a boiler inlet
sensor is installed.

Factory

Installer

0 to 252°F

(0 to 140°C)

BOILER DELTA T

Current temperature difference between the boiler outlet
sensor and the boiler inlet sensor.

Note: This item is only available when a boiler inlet
sensor is installed.

Factory

0 to 999

BOILER ON HOURS

The total number of running hours of the boiler since
this item was last cleared. Clear the numbers of hours

while viewing this item.

Factory

VIEW MENU

After the last item, the control returns to the first item in the menu.

The View menu items display current operating
temperatures and system status information.

Use the

Item button to view items in this menu.

Item

View Next Item