Mode 8 – External Direct Drive Operation

Mode 8 – External Direct Drive Operation

The control receives a heat demand provided via an
external analog input signal from a tekmar sequencing
control (such as a 275). The control turns on the boiler
pump and the Stage 1, 2, 3 and 4 contacts according to
the external input signal.

Mode 8 – External Direct Drive Operation - View Menu

BTC

Mode 8

External

Control

BTC

0-10 V (dc)

Direct Drive

Factory

Installed

Boiler

Outlet

Sensor

Factory

Installed

Boiler

Outlet

Sensor

Boiler Inlet Sensor (Optional)

External

Control

Sensor

s

s

e

c

c

A

n

o

i

t

p

i

r

c

s

e

D

e

g

n

a

R

d

l

e

i

F

m

e

t

I

14 to 266°F

(-10 to 130°C)

BOILER OUTLET

Current boiler outlet water temperature as measured
by the boiler outlet sensor.

Factory

Installer

14 to 266°F

(-10 to 130°C)

BOILER INLET

Current boiler inlet water temperature as measured by
the boiler inlet sensor.

Note: This item is only available when a boiler inlet
sensor is installed.

Factory

Installer

0 to 252°F

(0 to 140°C)

BOILER DELTA T

Current temperature difference between the boiler outlet
sensor and the boiler inlet sensor.

Note: This item is only available when a boiler inlet
sensor is installed.

Factory

0 to 999

BOILER ON HOURS

The total number of running hours of the boiler since
this item was last cleared. Clear the numbers of hours
by pressing and holding the and buttons together
while viewing this item.

Factory

VIEW MENU

After the last item, the control returns to the first item in the menu.

The View menu items display current operating
temperatures and system status information. Use the
Item button to view items in this menu.

Item

View Next Item