Adjus t menu – Slant/Fin EM-10 Service Manual User Manual

Page 20

Advertising
background image

20

EM-40-SM Service Manual

Mode 3 – Dedicated DHW with Parallel Piping - Adjust Menu (1 of 2)

Item Field

Range

Description

Access

Setting

1 to 8

MODE

Select the operating mode for the control.

Factory

Installer

PId or P

STAGE MODE

Select the staging operation to be either
automatic or manual.
(PId = automatic)
(P = proportional)

Factory

Installer

OFF, 70 to

190°F

(21 to 88°C)

TANK TARGET

Select the dedicated domestic hot water
tank target temperature.

Factory

Installer

Au, 2 to 10°F

(1 to 6°C)

TANK DIFFERENTIAL

Select the dedicated domestic hot water tank
differential. The DHW sensor temperature
must fall below this setting before the
boiler will turn on.

Factory

Installer

120 to 225°F

(49 to 107°C)

BOILER OUTLET MAXIMUM

S e l e c t th e m a x i m u m b o i l e r o u t l et
temperature. Exceeding this temperature
shuts off the boiler.

Factory

0:00 to 3:00 min

(1 second

increments)

FIRE DELAY

Select the amount of time required for
combustion pre-purging, ignition and the
flame to be established.
Note: This setting is only available when
STAGE MODE is set to Pld.

Factory

1 (Lo) or

2 (Med) or

3 (Hi)

BOILER MASS

Select the thermal mass of the boiler.
Note: This setting is only available when
STAGE MODE is set to PId.

Factory

Installer

ADJUS

T MENU

Continued on next page.

The Program menu items are the programmable settings
used to operate the system. Press and hold all three
buttons simultaneously
to enter the Program menu.

Item

Item

Change Value

Next Item

Enter Adjust Menu

Default

Setting 4

NOT VALID

FOR ELECTRIC

BOILER

APPLICATION