Technical data – Slant/Fin EM-10 Service Manual User Manual

Page 36

Advertising
background image

SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600

FAX: (516) 484-5921

Canada: Slant/Fin

LTD/LTEE

, Mississauga, Ontario

www.slantfin.com

©Slant/Fin Corp. 2014.

Technical Data

EM-10 Electric Boiler Temperature Control

Packaged weight

— 0.38 lb. (170 g)
— Enclosure D, black noryl plastic

Dimensions

— 4-3/4” H x 2-7/8” W x 1-7/8” D (120 x 74 x 48 mm)

Approvals

— ANSI Z21.23, CAN 1-6.6-M78-R2001, UL873, UL840

Ambient conditions

— Indoor use only, -40 to 140°F (-40 to 60°C),

< 90% RH non-condensing

Power supply

— 24 V (ac) ±10% 50/60 Hz 75 VA

Pump / Stage 1 Relays

— 120 V (ac) 5 A 1/6 hp pilot duty 240 VA

Stage 2, 3, 4 Relays

— 120 V (ac) 3 A 1/6 hp pilot duty 240 VA

Demands

— 24 to 120 V (ac) 2 VA

Sensors

— NTC thermistor, 10 kø @ 77°F (25°C ±0.2°C) ß=3892

included:

— 1 of Universal Sensor 071 with 96" long wires (S/F P/N 790400000)

Outdoor Sensor 070 (S/F P/N 339070000)

Factory Installed:

— Universal Sensor 071