EM-40-SM Service Manual

Applications

Mode 4 and 5 – Outdoor Reset and Setpoint Operation

Mode 4 – Outdoor Reset and Setpoint with Parallel
Piping

The control receives a heat demand provided from zone
valve end switches or a switching relay end switch. The
control turns on the boiler pump and operates the boiler to
maintain the outdoor reset boiler temperature at the boiler
outlet sensor. The control receives a setpoint demand from
a DHW aquastat. The control turns on the boiler pump and
operates the boiler to maintain the setpoint boiler target
temperature at the boiler outlet sensor whenever a setpoint
demand is present.

Note:

An external relay is required to operate the DHW

pump and provide DHW priority if required by disabling
the boiler pump.

Mode 5 – Outdoor Reset and Setpoint with Primary
– Secondary Piping

The control receives a heat demand provided from zone
valve end switches or switching relay end switch. The
control turns on the boiler pump and operates the boiler to
maintain the outdoor reset target temperature at the boiler
supply sensor. The control receives a setpoint demand
from a DHW aquastat. The control turns on the boiler pump
and operates the boiler to maintain the setpoint boiler
target temperature at the boiler supply sensor whenever a
setpoint demand is present.

Note:

An external relay is required to operate the DHW

pump and provide DHW priority if required by disabling the
system pump or zone pumps.

BTC

Mode 4

Relay

Outdoor

Sensor

Boiler Inlet Sensor (Included)

Factory

Installed

Boiler

Outlet

Sensor

BTC

Mode 5

Outdoor

Sensor

Relay

Factory

Installed

Boiler

Outlet

Sensor

Boiler Inlet Sensor (Optional)

Secondary

Piping

Sensor

(Included)