17

EM-40-SM Service Manual

Mode 1 and 2 – Two Setpoint Operation - Adjust Menu (1 of 2)

Item Field

Range

Description

Access

Setting

1 to 8

MODE

Select the operating mode for the control.

Factory

Installer

PId or P

STAGE MODE

Select the staging operation to be either
automatic or manual.
(PId = automatic)
(P = proportional)

Factory

Installer

OFF,

70 to 220°F

(21 to 104°C)

BOILER TARGET 1

Select the boiler target temperature while a
heat demand is present.

Factory

Installer

OFF,

70 to 220°F

(21 to 104°C)

BOILER TARGET 2

Select the boiler target temperature while a
setpoint demand is present.

Factory

Installer

120 to 225°F

(49 to 107°C)

BOILER OUTLET MAXIMUM

S e l e c t t h e m a x i m u m b o i l e r o u t l et
temperature. Exceeding this temperature
shuts off the boiler.

Factory

120 to 225°F

(49 to 107°C),

OFF

BOILER MAXIMUM

S e l e c t t h e m a x i m u m b o i l e r t a r g et
temperature.

Factory

OFF,

80 to 180°F

(27 to 82°C)

BOILER MINIMUM

S e l e c t t h e m i n i m u m b o i l e r t a r g e t
temperature.

Factory

0:00 to 3:00 min

(1 second

increments)

FIRE DELAY

(Not valid for electric boiler application)

Select the amount of time required
for combustion pre-purging, ignition
a n d t h e f l a m e t o b e e s t a b l i s h e d .
Note: This setting is only available when
STAGE MODE is set to PId.

Factory

1 (Lo) or

2 (Med) or

3 (Hi)

BOILER MASS

Select the thermal mass of the boiler.
Note: This setting is only available when
STAGE MODE is set to PId.

Factory

Installer

ADJUS

T MENU

Continued on next page.

The Program menu items are the programmable settings
used to operate the system. Press and hold all three
buttons simultaneously
to enter the Program menu.

Item

Item

Change Value

Next Item

Enter Adjust Menu

Default

Setting 4

NOT VALID

FOR ELECTRIC

BOILER

APPLICATION