Slant/Fin EM-10 Service Manual User Manual

Page 33

Advertising
background image

33

EM-40-SM Service Manual

Error Messages (1 of 2)

E01

The control was unable to read a piece of information from its EEPROM memory. The
control will stop operation until all settings in the Adjust menu have been checked by the
user or installer. To clear the error message, set Access Level DIP Switch A to Factory
(on position), then check all Adjust menu items.

BOILER OUTLET SENSOR SHORT CIRCUIT

The control is no longer able to read the boiler outlet sensor due to a short circuit. In this
case, if the boiler inlet sensor is present and operational, the control will operate using
the boiler inlet sensor. Otherwise, the control will not operate the boiler.
Test the boiler outlet sensor and related wiring. The error message will clear once the
error condition is corrected and a button is pressed.

BOILER OUTLET SENSOR OPEN CIRCUIT

The control is no longer able to read the boiler outlet sensor due to an open circuit. In this
case, if the boiler inlet sensor is present and operational, the control will operate using
the boiler inlet sensor. Otherwise, the control will not operate the boiler.
Test the boiler outlet sensor and related wiring. The error message will clear once the
error condition is corrected and a button is pressed.

BOILER INLET SENSOR SHORT CIRCUIT

The control is no longer able to read the boiler inlet sensor due to a short circuit. In this
case, the control will continue operation.
Test the boiler inlet sensor and related wiring. The error message will clear once the error
condition is corrected and a button is pressed.

BOILER INLET SENSOR OPEN CIRCUIT

The control is no longer able to read the boiler inlet sensor due to an open circuit. In this
case, the control will continue operation.
Test the boiler inlet sensor and related wiring. The error message will clear once the error
condition is corrected and a button is pressed.

BOILER SUPPLY SENSOR SHORT CIRCUIT

The control is no longer able to read the boiler supply sensor due to a short circuit. In
this case, if the boiler outlet sensor is operational, the control will operate based on the
boiler outlet sensor. If the boiler outlet sensor is not available and the boiler inlet sensor is
present and operational, the control will operate using the boiler inlet sensor. Otherwise,
the control will not operate the boiler.
Test the boiler supply sensor and related wiring. The error message will clear once the
error condition is corrected and a button is pressed.

BOILER SUPPLY SENSOR OPEN CIRCUIT

The control is no longer able to read the boiler supply sensor due to an open circuit. In
this case, if the boiler outlet sensor is operational, the control will operate based on the
boiler outlet sensor. If the boiler outlet sensor is not available and the boiler inlet sensor is
present and operational, the control will operate using the boiler inlet sensor. Otherwise,
the control will not operate the boiler.
Test the boiler supply sensor and related wiring. The error message will clear once the
error condition is corrected and a button is pressed.

OUTDOOR SENSOR SHORT CIRCUIT

The control is no longer able to read the outdoor sensor due to a short circuit. In this case
the control assumes an outdoor temperature of 32°F (0°C) and continues operation.
Test the outdoor sensor and related wiring. The error message will clear once the error
condition is corrected and a button is pressed.