EM-40-SM Service Manual

Mode 3 - Dedicated DHW with Parallel Piping

The control measures the tank temperature using
a DHW sensor. Once the tank temperature falls the tank
differential below the tank setpoint, an internal
heat demand is created. The boiler pump is turned on
and the boiler is operated to maintain the tank target
temperature.

Application

Mode 3 – Dedicated Domestic Hot Water Tank with Parallel Piping

Mode 3 – Dedicated DHW with Parallel Piping - View Menu

s

s

e

c

c

A

n

o

i

t

p

i

r

c

s

e

D

e

g

n

a

R

d

l

e

i

F

m

e

t

I

- - - ,

35 to 266°F

(2 to 130°C),

OFF

TANK TARGET

The temperature that the control is trying to maintain
in the tank.

Factory

Installer

14 to 266°F

(-10 to 130°C)

BOILER OUTLET

Current boiler outlet water temperature as measured
by the boiler outlet sensor.

Factory

Installer

14 to 266°F

(-10 to 130°C)

BOILER INLET

Current boiler inlet water temperature as measured by
the boiler inlet sensor.

Note: This item is only available when a boiler inlet
sensor is installed.

Factory

Installer

0 to 252°F

(0 to 140°C)

BOILER DELTA T

Current temperature difference between the boiler outlet
sensor and the boiler inlet sensor.

Note: This item is only available when a boiler inlet
sensor is installed.

Factory

14 to 266°F

(-10 to 130°C)

TANK

Current domestic hot water tank temperature as measured
by the DHW tank sensor.

Factory

Installer

0 to 999

BOILER ON HOURS

The total number of running hours of the boiler since
this item was last cleared. Clear the numbers of hours
by pressing and holding the and buttons together
while viewing this item.

Factory

VIEW MENU

After the last item, the control returns to the first item in the menu.

The View menu items display current operating
temperatures and system status information.

Use the

Item button to view items in this menu.

Item

View Next Item

BTC

Mode 3

DHW

Tank

Sensor

Boiler Inlet Sensor (Included)

Factory

Installed

Boiler

Outlet

Sensor