Mode 4 and 5 – Outdoor Reset and Setpoint Operation - Adjust Menu (3 of 3)

Item Field

Range

Description

Access

Setting

0:10 to 5:00 min

MINIMUM ON TIME

Select the minimum amount of time that
the stage contact must remain on before it
is allowed to turn off.
Note: This setting is only available when
STAGE MODE is set to P.

Factory

0:10 to 5:00 min

MINIMUM OFF TIME

Select the minimum amount of time that
the stage contact must remain off before it
is allowed to turn back on.
Note: This setting is only available when
STAGE MODE is set to P.

Factory

OFF, 0:20 to

9:55 min, On

PUMP DELAY

Select the boiler pump purge time after
shutting off the boiler.

Factory

35 to 100°F
(2 to 38°C),

OFF

WARM WEATHER SHUT DOWN

Select the heating system warm weather
shut down for outdoor reset operation. Heat
demands are ignored once the outdoor air
temperature exceeds this setting.

Factory

Installer

°F or °C

TEMPERATURE UNITS

Select to display temperature in degrees
Fahrenheit or in degrees Celsius.

Factory

Installer

After the last item, the control returns to the first item in the menu.

ADJUS

T MENU

Default

Setting 65˚F