Adjus t menu – Slant/Fin EM-10 Service Manual User Manual

Page 25

Advertising
background image

25

EM-40-SM Service Manual

Mode 4 and 5 – Outdoor Reset and Setpoint Operation - Adjust Menu (2 of 3)

Item Field

Range

Description

Access

Setting

120 to 225°F

(49 to 107°C),

OFF

BOILER MAXIMUM

Select the maximum boiler target
temperature.

Factory

OFF,

80 to 180°F

(27 to 82°C)

BOILER MINIMUM

S e l e c t th e m i n i m u m b o i l e r t a r g et
temperature.

Factory

0:00 to 3:00 min

(1 second

increments)

FIRE DELAY

Select the amount of time required for
combustion pre-purging, ignition and the
flame to be established.
Note: This setting is only available when
STAGE MODE is set to Pld.

Factory

1 (Lo) or

2 (Med) or

3 (Hi)

BOILER MASS

Select the thermal mass of the boiler.
Note: This setting is only available when
STAGE MODE is set to PId.

Factory

Installer

Au, 0:30 to

9:55 min

STAGE DELAY

Select the minimum time delay between
stages.
Note: This setting is only available when
STAGE MODE is set to PId.

Factory

Installer

Au, 2 to 42°F

(1 to 23°C)

DIFFERENTIAL

Select the boiler differential.
Note: The automatic setting is only available
when STAGE MODE is set to Pld staging.

Factory

0 to 10°F

(0 to 6°C)

STAGE DIFFERENTIAL

Select the interstage temperature differential
between stages for proportional staging.
Note: This setting is only available when
STAGE MODE is set to P.

Factory

0:10 to 8:00 min

INTERSTAGE ON DELAY

Select the amount of time that must pass
once a stage has been turned on in order
to allow the next stage to turn on.
Note: This setting is only available when
STAGE MODE is set to P.

Factory

0:10 to 4:00 min

INTERSTAGE OFF DELAY

Select the amount of time that must pass
once a stage has been turned off in order
to allow the next stage to turn off.
Note: This setting is only available when
STAGE MODE is set to P.

Factory

ADJUS

T

MENU

Continued on next page.