Section 7.2- engine dc control system, Problem, Engine starts then shuts down after a few seconds – Generac Power Systems NP-40G User Manual

Page 107

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

_________ Section 7.2- ENGINE DC CONTROL SYSTEM

Problem

5-

Engine Starts Then Shuts Down After a Few Seconds

TEST 25- ISOLATE

STILL

CHECK ENGINE

OIL

TEST 26- TEST

THE CCG SYSTEM

— SHUTS ^

OIL LEVEL

1» LEVELS

OIL PRESSURE

DOWN

GOOD

SWITCH

DOES NOT SHUT DOWN

WITH CCG SYSTEM
ISOLATED

1

TEST 27-TEST CCG

SYSTEM

SEE SECTION
1.5 IN PARTI
FOR TEST
PROCEDURES

i

LOW OIL LEVEL

I

REPLENISH OIL

TEST 28- TEST

OIL TEMPERATURE

SWITCH

BAD

I

REPAIR WIRE 85 CIRCUIT

OR REPLACE SWITCH

GOODi

IF OIL PRESSURE IS LOW,

DETERMINE CAUSE AND CORRECT.

IF OIL TEMPERATURE IS HIGH,

DETERMINE CAUSE AND CORRECT.

SEE PROBLEMS 4,
6 & 7 ON PAGE 7.1-1

bad

REPLACE BAD SWITCH

Page 7.2-5

Advertising
This manual is related to the following products: