Section 6.2- ENGINE CONTROLLER BOARD

General

The Enalne Controller circuit board controls all

phases of engine operation, Including cranking,

starting, running ana shutdown.

The circuit board interconnects with other com­

ponents of the engine eiectricai system to turn

them on or off at the proper times.

The board is powered by fused 12 VDC battery

output, avaiiabie to the board via Wire 15.

Circuit Board Connections

The circuit board mounts a 15-pin receptacie

(J1). A 15-pin connector piug connects to this re­

ceptacle to Interconnect the board with other com­

ponents and circuits. In addition, a single pin ter­

minal Is provided on the board for connection of

Wire 15 (J3) and a single pin terminal for Wire 14

(J2).

Receptacle J1

This 15-pln receptacle Is shown In Figure 2, along

with a chart that identifies each pin, wire and func­

tion.

Receptacle J2

Wire 14 connects to Terminal J2. This terminal

and wire are electrically hot (12 volts DC) only when

the engine is cranking or running. Battery voltage

Is delivered to Terminal J2 when circuit board ac­

tion energizes a board-mounted run relay while

cranking or running.

Wire 14 DC output is delivered to (a) the engine

fuel pump and (b) the engine Ignition system. If an

optional remote panel Is used. Wire 14 DC output

will turn on a "RUN" lamp on that panel.

Receptacle J3

wire 15 connects to Terminal J3. This Is fused

battery voltage. The Wire 15 circuit Is electrically

hot at all times (provided the unit battery Is con­

nected).

Figure 2. Receptacle J1

10

11

12

13

14

15

WIRE

56

90

18B

17

66

85

18

ToncnsTT

Delivers 12 VDC to Starter Contactor

while cranking only.

Delivers 12 VDC to automatic choke

solenoid coll while cranking only.

Interconnects CCG circuit board so

that board can stop engine In the event

of a generator fault (NOTE 1).

Not used on computer-controlled

generator units.

Not used on computer-controlled

generator units.

When Wire 17 Is connected to ground

by holding Start-Run-Stop switch at

"START", cranking will occur.

Not used on computer-controlled

generator units.

Not used on computer-controlled

generator units.

Not used on computer-controlled

generator units.

AC signal from Stator battery charge

winding for starter cutout.

When grounded by Low Oil Pressure

or High oil Temperature switch, the

circuit board will stop engine.

Common frame ground.

Not used on Computer-controlled

generator units.

When Wire 17 Is connected to ground

by holding Start-Run-Stop switch at

"STOP^'i shutdown will occur.

Not used on computer-controlled

generator units.

NOTE 1:- See "AUTOMATIC SHUTDOWNS" In Section

1.2 (Page 1.2-5).