Oil Temperature Switch

(Continued)

NOTE: The CCG circuit board also has automatic

engine shutdown capability. The circuit board will

shut the engine down automatically on occurence

of (a) over-voltage, (bj under-voltage, (c) over­

speed, (di zero current failure, (e) converter failure,

or (ef) micro-processor failure, see Section 1.2.

Section 6.5- ENGINE PROTECTIVE DEVICES

TESTING;

See Figure 3. Remove the switch and piace its

sensing tip into oii. Place a thermometer into the

oil. Connect the test leads of a VOM across the

switch terminals. The meter should read "Infinity''.

Heat the oil. When oil temperature reaches

approximately 287<-296a F. (142a-147a C.), the

meter should read "continuity" (a small resistance

Is acceptable).

NOTE: The above procedure yjplles to OII

Temperature Switch Part No. 94090, rated 293^ F.

(14S‘ C.). Some early production units were

equipped with a 265‘ F. switch which caused

premature high temperature shutdowns. The 265^

F. switch should be removed and replaced with the

Part No. 94090 switch.