Section 1.4- INSULATION RESISTANCE

Drying the Generator

GENERAL:

If testing Indicates that the insulation resistance of a

winding Is below a safe value, the winding should be

dried before operating the unit Some recommended

drying methods include (a) heating units and (b) forced

air.

HEATING UNITS:

If drying Is needed, the generator can be enclosed In

a covering. Heating units can then be Installed to raise

the temperature about 15’-18* F. (8*-10* C.) above ambi­

ent.

FORCED AIR:

Portable forced air heaters can be used to dry the

generator. Direct the heated air Into the generator’s air

intake openings. Run the unit at no-load. Air temperature

at the point of entry Into the generator should not exceed

150* F. (66* C.).