Programmable Outputs

The BLUAC5 drives feature three digital outputs:
Y1/Brake: controls an electric brake relay, automati-
cally releasing and engaging as the drive requires
Y3/Fault: closes when a drive fault condition occurs.
The red and green LEDs will flash an error code.
Y2/In Position: indicates that the drive has achieved
a desired goal, such as a target position.

The BLUAC5-SE and -QE have four additional pro-
grammable outputs, located on the

IN/OUT 2 con-

nector

.

The outputs can be used to drive LEDs, relays and the inputs of other electronic devices like
PLCs and counters. The Y1/BRAKE, Y3/FAULT and Y2/INPOSN outputs can only sink cur-
rent. The YCOM terminal must be tied to power supply (-).

Diagrams for various connections follow.
Do not connect the outputs to more than 30VDC.

The current through each output terminal must not exceed 100 mA.

BLu Servo

YCOM

OUT+

5-24 VDC

Power Supply

+

Load

Sinking (High Side) Load

inside IN/OUT 1

Y1/BRAKE

YCOM

Y2/INPOSN

Y3/FAULT