Venting installation instructions – Desa (V)DVF36 User Manual

Page 16

Advertising
background image

www.desatech.com

56131-F

16

VENTING INSTALLATION

INSTRUCTIONS

Continued

Figure 26 - Installing Firestop

If area above is a living space, install
firestop below framed hole.

If area above is an attic, install firestop
above framed hole.

Note: Pay special attention to these installa-

tion instructions for required clearances (air

space) to combustibles when passing through

ceilings, walls, roofs, enclosures, attic rafters,

etc. Do not pack air spaces with insulation.

Also note maximum vertical rise of the vent-

ing system and any maximum horizontal

offset limitations. Offsets must fall within the

parameters shown in Figure 25.

2. Set the fireplace in desired location. Drop a

plumb line down from the ceiling to the posi-

tion of the fireplace exit flue. Mark the center

point where the vent will penetrate the ceiling.

Drill a small locating hole at this point.

Drop a plumb line from the inside of the roof

to the locating hole in the ceiling. Mark the

center point where the vent will penetrate the

roof. Drill a small locating hole at this point.

Flat Ceiling Installation

1. Cut a 12

1

/

2

" square hole in the ceiling using

the locating hole as a center point. The open-

ing should be framed to 12

1

/

2

"x12

1

/

2

" inside

dimensions, as shown in Figure 18 on page

13 using framing lumber the same size as the

ceiling joists. If the area above the ceiling is

an insulated ceiling or an attic, nail firestop

from the top side. This prevents loose insula-

tion from falling into the required clearance

space. If the area above the ceiling is a living

space, install firestop below the framed hole.

The firestop should be installed with no less

than three nails per side (see Figure 26).

2. Assemble the desired lengths of pipe and

elbows necessary to reach from the fireplace

flue up through the firestop. All connections

must be sealed with high temperature silicone

sealant as specified in the second warning

statement on page 11. Be sure all pipe and

elbow connections are fully twist-locked (see

Figure 17, page 13).

3. Cut a hole in the roof using the locating hole

as a center point. (Cover any exposed open

vent pipes before cutting hole in roof.) The

12

1

/

2

" x 12

1

/

2

" hole must be measured on

the horizontal; actual length may be larger

depending on the pitch of the roof. There

must be a 1" clearance from the vent pipe to

combustible materials. Frame the opening as

shown in Figure 18 on page 13.

4. Connect a section of pipe and extend up

through the hole. If an offset is needed to avoid

obstructions, you must support the vent pipe

every 3 feet. Use wall straps for this purpose

(see Figure 24, page 15). Whenever possible,

use 45° elbows instead of 90° elbows. The 45°

elbow offers less restriction to the flow of the

flue gases and intake air.

X

12

Roof Pitch is
x 1 Listed
Clearance

8'

Minimum

Listed
Vent Cap

Lowest
Discharge
Opening

Listed
Gas
Vent

H (Min.) Height from Roof

Figure 25 - Vertical Vent Termination

Clearance

ROOF PITCH

H(Min.)

Flat to 6/1

1.0'

6/1 to 7/1

1.5'

Over 7/1 to 8/1

1.5'

Over 8/1 to 9/1

.0'

Over 9/1 to 10/1

.5'

Over 10/1 to 11/1

3.5'

Over 11/1 to 1/1

4.0'

Over 1/1 to 14/1

5.0'

Over 14/1 to 16/1

6.0'

Over 16/1 to 18/1

7.0'

Over 18/1 to 0/1

7.5'

Over 0/1 to 1/1

8.0'

Advertising