6. Set Line Test Interval: When all the lines have been programmed, and the results have been stored,

select the interval for the stand-alone self-commanded test. To do this, move the rotary line-select
switch to the time value according to Table 2 below.

Table 2.

Time Switch

Position

15 minutes

8

30 minutes

9

1 hour

A

2 hours

B

6 hours

C

8 hours

D

12 hours

E

24 hours

F

7. Then press and hold the button for 3 seconds until the fault LEDs begin flashing. The test interval is

now stored. N

OTE

: The factory-default test interval is 1 hour.

8. Remove the JU1 programming jumper.