Gasboy CFN Site Controller User Manual
Page 53

Pump Interface Manual v1.3
Wayne
45
03/20/03
Gasboy CFN Series
•
If prices were loaded in the dispensers with a Wayne Console, they may have
to be removed before the dispensers will work properly.
•
If the problems occurred after a dispenser’s Price Codes were changed,
REBOOT the Site Controller and cycle power to the dispenser.
After a price change, prices do not change at the dispensers and/or all or some of the hoses
won’t reset.
(Keep in mind that it is normal for the prices not to change until the dispenser has been
authorized and goes through reset.)
Possible cause: Communication errors with Interface. May need to clear the RAM on the
Wayne 2400 CPU and REBOOT the Site Controller.
Unassigned transactions or “Malloc out of buffer” crashes when the Wayne EC Cabinet is
connected to the SCII.
Possible cause: Bad or wrong revision PIB/Plus board in the Wayne EC Cabinet.