Jumpers, I/o board – Gasboy CFN Site Controller User Manual
Page 64

56
Pump Control Unit
Pump Interface Manual v1.3
Gasboy CFN Series
03/20/03
DIP Switch Bank C
Jumpers
I/O Board
The part number of the original PPC I/O board is C05668.
Address
B-1
B-2
B-3
B-4
B-5
B-6
1
cl
cl
cl
cl
cl
cl
2
op
cl
cl
cl
cl
cl
3
cl
op
cl
cl
cl
cl
4
op
op
cl
cl
cl
cl
5
cl
cl
op
cl
cl
cl
6
op
cl
op
cl
cl
cl
7
cl
op
op
cl
cl
cl
8
op
op
op
cl
cl
cl
9
cl
cl
cl
op
cl
cl
10
op
cl
cl
op
cl
cl
11
cl
op
cl
op
cl
cl
12
op
op
cl
op
cl
cl
13
cl
cl
op
op
cl
cl
14
op
cl
op
op
cl
cl
15
cl
op
op
op
cl
cl
16
op
op
op
op
cl
cl
Baud Rate
B-7
B-8
not used
closed
closed
9600
open
closed
1200
closed
open
300
open
open
Position & Definition
Setting(*=customary)
1-4
pulser enabled
pumps 1-4
*closed=after reset is complete
open=upon activation
5
CRC required
*open=required
closed =not required
6
dead man timer
*always open=enabled
7
____
8
test mode
*closed=no
open=yes
Jumper
Setting-IN
Setting-OUT
Default
K1
normal
battery test
installed
K2
battery
no battery
installed