Troubleshooting, Motor overamps, Too much airflow – Greenheck IGK (472084) User Manual

Page 12

Advertising
background image

12

Model IGK Make-Up Air

®

Motor Overamps

Troubleshooting

Air volume too high?

Adjust drives or increase external

static pressure as needed.

(Reference Blower Start-Up step #5)

Motor horsepower too low?

Resize motor.

Motor voltage correct?

Provide proper power supply.

(Reference Blower Start-Up step #1)

Blower rotation correct?

Reverse blower rotation.

(Reference Blower Start-Up step #2)

Actual static pressure

lower than design?

Adjust drives to reduce blower RPM.

(Reference Blower Start-Up step #5)

No

No

Yes

Yes

Yes

Yes

No

Yes

No

No

Shorted windings in motor?

Replace motor.

Yes

Everything is working

properly, consult factory.

Yes

Too Much Airflow

Blower speed too high?

Adjust drives as needed.

(Reference Blower Start-Up step #5)

Insufficient external static

pressure?

Increase external static pressure.

Filters not in place?

Install filters.

Yes

Yes

Yes

No

No

Everything is working properly,

consult factory.

No

Advertising