Model IGK Make-Up Air

®

Installation of Gas Piping

IMPORTANT

All gas piping must be installed in accordance
with the latest edition of the National Fuel Gas
Code ANSI/Z223.1 and any local codes that may
apply. In Canada, the equipment shall be installed
in accordance with the Installation Code for Gas
Burning Appliances and Equipment (CGA B149) and
Provincial Regulations for the class. Authorities
having jurisdiction should be consulted before
installations are made.

IMPORTANT

All piping should be clean and free of any foreign
material. Foreign material entering the gas train can
cause damage.

WARNING

All components of this or any other gas fired heating
unit must be leak tested prior to placing the unit
into operation. A soap and water solution should be
used to perform this test. NEVER test for gas leaks
with an open flame.

IMPORTANT

Do NOT connect the unit to gas types other than
what is specified and do NOT connect the unit to
gas pressures that are outside of the pressure range
shown on the label.

WARNING

When leak testing pressures equal to or less than
14 in. wc (3.5 KPa), first close the field-installed
shutoff valve to isolate the unit from the gas supply
line.

NOTE

When connecting the gas supply, the length of the
run must be considered in determining the pipe size
to avoid excessive pressure drop. Refer to a Gas
Engineer’s Handbook for gas pipe capacities.

NOTE

Each furnace has a single 3/4-inch connection.

1. Determine the Supply Gas
Requirements

The unit’s nameplate states the requirements for the
gas being supplied to the unit.

4. Test the System for Leaks

Check both the supply lines and the factory piping for
leaks. Apply a soap and water solution to all piping
and watch for bubbling which indicates a leak.

WARNING

NEVER test for a gas leak with an open flame.

WARNING

The factory piping has been checked for leaks, but
should be rechecked due to shipping and installation.

To

Controls

Gas Cock

From

Gas

Supply

6 in. Trap

1/8 in. Plugged Tap

Ground Joint Union

Supply Gas Line

2. Install Additional Regulator if Required

When the supply gas pressure exceeds the maximum
gas pressure shown on the unit’s nameplate, an
additional regulator (by others) is required to reduce
the pressure. The regulator
must have a listed leak
limiting device or it must
be vented to
the outdoors.

Supply Gas Pressure Range

(inches wc)

Minimum

Maximum

Natural

6

14

LP

10

14

3. Connect the Supply Gas Line

A manual shut off valve (gas cock), 1/8 inch plugged
test port and 6 inch drip leg must be installed prior
to the gas train. The valve and the test port must be
accessible for the connection of a test gauge. Supply
gas connections must be made by a qualified installer
and are not furnished by
Greenheck.

Direct Gas Nameplate

Maximum gas pressure

Type of gas

Normal manifold pressure

“W.C.

“W.C.

“W.C.

F

PSI

“W.C.

MAX BTU/HR
BTU/H MAX

NORMAL MANIFOLD
PRESSURE
PRESSION DÕADMISSION
NORMALE

MIN GAS
PRESSURE
PRESSION DE GAZ

TYPE OF GAS
NATURE DU GAZ

MIN BTU/HR
BTU/H MIN

MIN GAS PRESSURE
FOR MAX OUTPUT
PRESSION DE GAZ MIN
POUR PUISSANCE MAX

MAX GAS
PRESSURE
PRESSION DE GAZ
MAX

DESIGN

DT

DT NORMALE

EQUIPPED FOR

CONCU POUR

SCFM

“W.C.

EXTERNAL STATIC PRESSURE

PRESSION STATIQUE EXTERIEURE

AGAINST

CONTE

Minimum gas pressure