Model IGK Make-Up Air

®

Installation - Electrical Wiring

IMPORTANT

Before connecting power to the unit, read and
understand the following instructions and wiring
diagrams. Complete wiring diagrams are attached
on the inside of the control center door(s).

IMPORTANT

All wiring should be done in accordance with the
latest edition of the National Electric Code ANSI/
NFPA-70 and any local codes that may apply. In
Canada, wiring should be done in accordance with
the Canadian Electrical Code.

CAUTION

If replacement wire is required, it must have a
temperature rating of at least 105ºC, except for
energy cut-off or sensor lead wire which must be
rated to 150ºC.

IMPORTANT

The equipment must be properly grounded. Any
wiring running through the unit in the airstream must
be protected by metal conduit, metal clad cable or
raceways.

DANGER

High voltage electrical input is needed for this
equipment. This work should be performed by a
qualified electrician.

CAUTION

Any wiring deviations may result in personal injury
or property damage. Greenheck is not responsible
for any damage to, or failure of the unit caused by
incorrect final wiring.

IMPORTANT

Greenheck’s standard control voltage is 24 VAC.
Control wire resistance should not exceed 0.75 ohms
(approximately 285 feet total length for 14 gauge
wire; 455 feet total length for 12 gauge wire). If the
resistance exceeds 0.75 ohms an industrial-style,
plug-in relay should be wired in place of the remote
switch. The relay must be rated for at least 5 amps
and have a 24 VAC coil. Failure to comply with these
guidelines may cause motor starters to chatter or
not pull in, resulting in contactor failures and/or
motor failures.

1. Determine the Size of the Main Power

Lines

The unit’s nameplate states the voltage and the unit’s
total MCA. The main power lines to the unit should be
sized accordingly. The nameplate is located on the
outside of the unit on the control panel side.

2. Provide the Opening(s) for the
Electrical Connections

Electrical openings vary by unit size and arrangement
and are field supplied.

3. Connect the Main Power

Connect the main power lines to the disconnect
switch and main grounding lug(s). Torque field
connections to 20 in-lbs. See the Control Center
Layout in the Reference section for main disconnect
and grounding lug(s) locations.

4. Wire the Optional Convenience Outlet

The convenience outlet requires a separate 115V
power supply circuit. The circuit must include short
circuit protection which may need to be supplied by
others.

5. Wire the Optional Accessories

Reference the ladder diagram on the inside of the
control center door for correct wiring of the following
accessories:

• Blower Switch
• Heat Switch
• Remote Panel (KSCP)

SUP HP

MCA

EXH HP

MOP

VOLTS

HZ

PH

Unit’s Total MCA

Voltage, Hertz, Phase

SUP HP

MCA

EXH HP

MOP

VOLTS

HZ

PH

Voltage, Hertz, Phase