Troubleshooting, Insufficient airflow – Greenheck IGK (472084) User Manual

Page 14

Advertising
background image

14

Model IGK Make-Up Air

®

Troubleshooting

Insufficient Airflow

Damper not fully opened?

24 VAC between ST1 (AUX)

terminal 53 and X?

24 VAC between ST1 (AUX)

terminal 53 and X?

Adjust damper linkage or replace faulty actuator.

(Damper actuator may take a few minutes to open)

Damper transformer (TR2) fault

(Replace transformer TR2)

Supply starter auxiliary contact

(ST1 (AUX)) defective

(Replace auxiliary contactor)

Filters dirty or clogged

Clean or replace filters.

(Reference Filter Maintenance in the Maintenance section).

Blower speed too low?

Adjust drives as needed.

(Reference Blower Start-Up step #5)

System static losses too high?

Reduce losses by improving ductwork.

Yes

Yes

Yes

No

Yes

No

No

No

No

No

Leaks in ductwork

Repair leaks.

Yes

Belt slipping

Replace or tighten belt.

(Reference V-Belt Maintenance in the Maintenance section)

Yes

Everything is working properly,

consult factory.

Yes

Yes

Yes

No

Advertising