15 | GS Series Installation

UL Listed Cap

(by others)

Flashing,

4 in. (10 cm) min.

air space between

piping and combustible

materials

BH Vent

Maintain diameter of

exhaust outlet,

any combination of

vertical up / horizontal run,

max 100 ft (30 m),

slope 1/4 in./ft (2 cm/m).

2 ft (60 cm) min.
above any ridge
within 10 ft (3 m)

3 ft (90 cm)

min. above roof

Drain
(Note: Condensate
may require treatment,
consult local codes)

Support venting so

that weight is not

on exhaust outlet.

Condensate tee

(by others)

within 2 ft (60 cm)

of unit.

2 ft (30 cm)

min.

BH Vent Exhaust

Exhaust outlet
Install male to male
adapter (by others).

Terminate
Vertically

Horizontally

or

Horizontal exhaust
terminal must be
certified and can be
ordered from Nortec. If
BH venting used, orient
vertically, 6 in from wall.

Chose only one terminal
location (2 shown for
illustration only)







Figure 10: Vertical and Horizontal Venting Using BG Type With Sealed Combustion





Figure 9: Vertical and Horizontal Venting Using BH Type