21 | GS Series Installation

Wall or Duct Mounted Modulating Humidistat: Provides a modulating signal to the unit that represents the
output (up to 100%) required from the humidifier. Signal type can be changed in the field.

All GS models may be configured for either single or dual channel modulation. Control signals can be 0-10
VDC or 0-20 mA (0-5 VDC, 1-5 VDC, 4-20 mA and 2-10 VDC are also available). The unit must be ordered
from the factory for the desired signal type and number of channels. When configured for 2-channel
modulation the humidifier will generate steam only if both channels indicate a demand. If both channels are
demanding steam the humidifier will satisfy the lower demand signal.

Table 4: Current and Breaker Requirements for GS Series Units

Voltage (V)

Rated Amps (A)

Suggested Breaker (A)

GSTC/GSP 100 Indoor

120

2.1

15

208-240

1.1

15

GSTC/GSP 200 Indoor

120

3.7

15

208-240

1.9

15

GSTC/GSP 300 Indoor

120

5.3

15

208-240

2.7

15

GSTC/GSP 400 Indoor

120

6.8

15

208-240

3.5

15

GSTC/GSP 500 Indoor

120

8.4

15

208-240

4.3

15

GSTC/GSP 600 Indoor

120

10

15

208-240

5.2

15

GSTC Outdoor 100

120

6.3

15

208-240

3.2

15

GSTC Outdoor 200

120

7.4

15

208-240

4

15

GSTC Outdoor 300

120

13.7

20

208-240

6.9

15

GSTC Outdoor 400

120

15.2

20

208-240

7.7

15

GSTC Outdoor 500

120

21

30

208-240

10.6

15

GSTC Outdoor 600

120

22.6

30

208-240

11.5

15