Nortec GS Series User Manual

Page 77

Advertising
background image

GS Series Installation | 74


FTW:FILL
WARNING


The fill valve has
been active for an
extended length of
time and the water
level is still zero


Fill valve remains
activated. Warning
will change to fault
if float level
remains at zero.


(1) Ensure water line is open and that

adequate water supply and pressure

is available.

(2) Check wiring to float board and

fill valve. Check strainer on fill valve inlet.

(3) Check that drain valve, auxiliary

drain valve or manual drain switch

are not activated.

(4) Check fill valve using diagnostic

output test. Consult Factory.


RHW:RH HIGH
WARNING


The measured RH is
above the RH High
alarm setting.


The humidifier will
remain idle until
the measured RH
drops below
setpoint.


(1) Check that RH high setting is correct

for the application.

(2) Check sensor location (too close to steam

distributor or other sources that affect

measurement).

(3) System may be oversized.

Lower manual capacity of the unit.

(4) Consult Factory.


RLW:RH LOW
WARNING


The measured RH is
below the “RH Low”
alarm setting.


The humidifier
should be
operating unless in
standby or lockout
mode.


(1) Check that RH low setting is correct

for the application.

(2) Check sensor location (too close to door,

window, or other sources that affect

measurement).

(3) Humidifier may be in lockout or standby.

Check security loop. Check that all burners

operational.

(4) System may be undersized. Check manual capacity

setting. Consult factory.


RMW:RH LIMIT
WARNING


The RH input
is lower than 3%.


Operation is
interrupted until an
input higher than
3%
is received.


(1) Check connection between sensor and

unit.

(2) Check that sensor is functional.

(3) Ensure controls are located such that

they provide accurate readings.

(4) Consult factory.


NSW:NO
SIGNAL
WARNING


No communication
is detected from
Master unit.
(This unit is set up
as slave)


Operation is
interrupted until
signal is received.


(1) Verify that one unit is configured as

master.

(2) Check connection between master and slave.

(3) Consult factory.


RDW: REMOTE
DISABLED


The unit has been
remotely disabled
through modbus
communication or
Nortec Online.


Operation is
interrupted until
unit is re-enabled
via modbus or
software.


(1) Enable unit through building management

system (BMS) or Nortec Online.

(2) If unit cannot be enabled remotely,

try enabling unit under software

Modbus Settings.

(3) Consult factory.


NBW: NO
BURNERS
AVAIL


All burners have been
disabled via software.
No burners are
available for operation.


The unit will not be
able to respond to
a demand until 1 or
more burners are
enabled.


Advertising