Idle only: humidifier is on standby – Nortec GS Series User Manual

Page 69

Advertising
background image

GS Series Installation | 66

User Defined Setting
BD rate

: 25

FTBD

: On

FTBD Time

: 23:30

FTBD Hours

: 100

Idle Mode

: Idle Drain

Idle Drain

: 72

Esc

Set

FTBD Time
Hour

: 23

Minute

: 30

Esc

Set

FTBD Time

: 23:30

Hour : 23

Full Tank Blow Down Time
Set the desired time of day to
completely drain the tank and refill.

Note: Since the FTBD interrupts
humidifier operation, it is
recommended to set time outside
peak operation time.

User Defined Setting
FTBD

: On

FTBD Time

: 23:30

FTBD Hours

: 100

Idle Mode

: Idle Drain

Idle Drain

: 72

Fill Corr

: 100

Esc

Set

FTBD Hours

100 h

100 h

Esc

Set

FTBD Hours

: 100

Full Tank Blow Down Interval
Set the desired weighted time
interval between FTBDs.

Idle Mode
Idle Drain
Idle Only
Idle Drain
Keep Warm

Esc

Set

Idle Drain

User Defined Setting
FTBD Time

: 23:30

FTBD Hours

: 100

Idle Mode

: Idle Drain

Idle Drain

: 72

Fill Corr

: 100

Drain Corr

: 100

Esc

Set

Idle Mode

: Idle Drain

Idle Mode
Configures humidifier operation
when there is no call for humidity.

Idle Only: Humidifier is on standby.

Idle Drain: Humidifier drains after
specified idling time (see Idle Drain).

Keep Warm: Water in tank is kept
between 140-160ºF (60 -70ºC)

User Defined Setting
Idle Mode

: Idle Drain

Idle Drain

: 72

Fill Corr.

: 100

Drain Corr.

: 100

Float Ck

: 23:30

Date

: 01/01/09

Esc

Set

Fill Correction
100 %
100 %

Esc

Set

Fill Corr

: 100

Fill Correction
Adjust the fill on and fill off times.
Values above 100% will increase
the fill on time and values below
100% decrease fill on time.

User Defined Setting
Idle Drain

: 72

Fill Corr.

: 100

Drain Corr.

: 100

Float Ck

: 23:30

Date

: 01/01/09

Time

: 12:00:00

Esc

Set

Drain Correction
100 %
100 %

Esc

Set

Drain Corr

: 100

Drain Correction
Used to compensate for variation in
drain pump flow rates. The drain
correction adjusts the actual drain
duration by drain time. Increasing
drain correction increases drain
duration and decreasing correction
decreases drain time.

Advertising