61 | GS Series Installation

CNT Band

CNT Band should not normally be changed.
The CNT Band setting adjusts the band
within which the humidifier will modulate
between 0 and 100% output. (Default =
15%)

Int Time

Int Time should not normally be changed. Int
Time adjusts the frequency at which the
controller corrects for proportional control
error. It is only displayed if REG Mode is set
to RH (PI)

LIM Set-P

Sets the duct high limit setpoint value. As
RH in the duct approaches the high limit the
output of the humidifier will be throttled
back to prevent wetting the duct. (Default =
80%)

LIM Band

Should not normally be changed. The LIM
Band setting adjusts the band within which
the humidifier will throttle down the
humidifier output from 100 to 0%. (Default
= 15%)

Limit Damping

Sets the number of seconds the sensed RH
must exceed the limit band before output is
throttled down. (Default = 5 s)

Control Band
15% RH

15% RH