Nortec GS Series User Manual

Page 96

Advertising
background image

93 | GS Series Installation

Table 17: GS Quick Reference

Item

GS 100

GS 200

GS 300

GS 400

GS 500

GS 600

Gas Pressure

Natural Gas min (in wc/mbar)

4.5/11.2

Natural Gas max (in wc/mbar)

9/22.4

Propane min (in wc/mbar)

9/22.4

Propane max (in wc/mbar)

13/32.3

Min free air opening (in/cm)

13/33

23/58

35/89

47/119

59/150

71/180

Input

Max (BTU)

140,000

280,000

420,000

560,000

700,000

840,000

Min GSTC (BTU)

45,000

Direct vent min (BTU)

60,000

Gas Piping Size (in/cm)

1/2/1.3

3/4/1.9

1/2.5

1/2.5

1.25/3.2

1.25/3.2

"BH" Vent

X

X

X

X

X

X

"B" Vent

X

X

X

X

X

X

"BH" Exhaust Piping (in/cm)

3/7.6

4/10.2

5/12.7

5/12.7

6/15.2

6/15.2

4/10.2

5/12.7

7/17.8

7/17.8

8/20.3

8/20.3

Appliance Category

I or III

I or III

I or III

I or III

I or III

I or III

Full Weight In (lbs/kg)

416/188

588/266

954/432

974/441

1340/607

1360/616

Empty Weight In (lbs/kg)

266/120

354/160

485/217

529/239

659/298

703/318

User level password

0335

Water consumption (25% bd)

Gallons/liters per hour

433/1639

866/3278

1300/4921

1733/6560

2166/8199

2600/9842

Tank Water Volume

Gallons/liters

18/71

29/111

58/221

55/210

84/320

81/309

Fill valve flow rates

To tank: Gallons/liters per minute

2.64/10

To float chamber: Gallons/liters
per minute

0.09/0.35

Supply water pressure

Min. (psi/kPa)

30/206

Max. (psi/kPa)

80/551

Drain rate (includes D.W.C)

Gallons/Litres per minute

5.2/20

Min drain pipe size (in/cm)

1 to 1.5 / 2.5 to 3.8 OD or larger

Power supply requirements

120 volts a/c

X

X

X

X

X

X

208-240 volts a/c 1PH

X

X

X

X

X

X

Steam Outlet size (in/cm)

1.75/4.4

3/7.6

3/7.6

4/10.2

4/10.2

4/10.2

Advertising