73 | GS Series Installation

Troubleshooting

Table 10: GSTC Warning Troubleshooting

GSTC Warning
Displayed


Description of Warning


Corrective action
by unit

Troubleshooting

IMW-X:IGNITION
FAIL

The Ignition module
identified has failed to
ignite within the allotted
time
(4 minutes).

The unit will index
to next available
burner in the
sequence.

(1) Check sight port of problematic burner. Watch for

hot igniter (glowing red) followed by a flame.

(2) If igniter not hot, check for voltage.

Check wiring. Replace igniter if necessary.

(3) If igniter is hot but no flame, ensure gas supply

connected. Check for 24V at gas valve.

(4) If flame visible, check flame sensor wiring.

Check L1 not wired to N. Consult Factory.


APW-X:AP OPEN
WARN


The air proving
switch identified has
opened while the
unit was operating.


Unit will interrupt
operation and retry
three times.

After a third try a
fault is generated.


(1) Ensure pressure tubes are secure. Check

wiring to A/P switch and to driver board.

(2) Ensure blower is operating. if not,

check wiring and power to blower.

Check blower relay.

(3) Perform blower diagnostic test to ensure A/P switch

remains closed during operation.

(4) Check for suction In pressure tubes. If

switch does not close it may be defective. Consult

Factory.


AOW-X:AP OPEN
WARN


The air proving switch
identified did not close
during blower start-up.


Unit will interrupt
operation and retry
three times.

After a third try a
fault is generated.


(1) Ensure pressure tubes are secure.

Check wiring to A/P switch and to driver

board.

(2) Ensure blower is operating. If not, check wiring and

power to blower. Check blower relay

.

(3) Perform blower diagnostic test to ensure A/P switch

remains closed during operation.

(4) Check for suction In pressure tubes. If

switch does not close it may be defective.

Consult Factory.


BHW-X:BLOWER
RPM HIGH


The indicated blower
has an RPM higher
than the lead blower
by more than the
allowable tolerance.


The unit will keep
monitoring blower
RPM and display
this warning if RPM
remains high.


(1) Ensure pressure tubes are secure.

Check wiring to A/P switch and to driver

board.

(2) Ensure blower is operating. If not check wiring and

power to blower. Check blower relay.

(3) Perform blower diagnostic test to ensure A/P switch

remains closed during operation.

(4) Check for suction In pressure tubes. If

switch does not close it may be defective.

Consult Factory.


BLW-X:BLOWER
RPM LOW


The indicated blower
has an RPM lower
than the lead blower
by more than the
allowable tolerance.


The unit will keep
monitoring blower
RPM and display
this warning if RPM
remains low.


(1) Ensure blower in question is securely

connected and is receiving correct

voltage.

(2) Verify blower control wiring connection.

Check blower diagnostic test for abnormalities.

(3) Ensure no restriction on blower.

Ensure no blockage of blower inlet.

(4) Blower speed may decrease due to wear. Safe to operate but

output may be reduced. Order new blower.


HMW: MAINT.
WARNING


The preset service
interval time has
expired.


The unit will
continue to run for
200 hours before a
fault is generated.


(1) Service unit. Consult maintenance

guide in the Nortec manual.

(2) Reset service interval time after

maintenance has been completed.