Protective Conductor / Touch Current Limits

47

Protective Conductor / Touch Current Limits

Appliance Class

Maximum Current

Portable or hand held Class I

equipment

0.75mA

Class I heating appliances

0.75mA or 0.75mA per kW,

whichever is the greater with a

maximum of 5mA

Other Class I equipment

3.5mA

Class II equipment

0.25mA

Class III equipment

0.5mA

Copies of the IEE ‘Code of Practice for In-Service Inspection and
Testing of Electrical Equipment ‘ may be obtained from:

The Institution of Electrical Engineers
P.O. Box 96
Stevenage,
Herts SG1 2SD
ISBN 0 85296 776 4