Protective Conductor / Touch Current Limits
47
Protective Conductor / Touch Current Limits
Appliance Class
Maximum Current
Portable or hand held Class I
equipment
0.75mA
Class I heating appliances
0.75mA or 0.75mA per kW,
whichever is the greater with a
maximum of 5mA
Other Class I equipment
3.5mA
Class II equipment
0.25mA
Class III equipment
0.5mA