Coa connection (supv), Disabled, Dial – Verilink PRISM 3002 (34-00277) Product Manual User Manual

Page 45: Direct, Primary dial string and secondary dial string, Initialization string, Disconnect string, Coa connection (supv) -23, Disabled -23 dial -23 direct -23

Advertising
background image

Configuration Screens

4-23

Element ID HH:MM:SS MM/DD/YY <CR> <LF>

NET Alarms: alarms <CR> <LF>

DTE Alarms: alarms <CR> <LF>

where (alarms) is a string consisting of some or all of the identifiers LOS, OOF,
RAS, AIS, UAS, ERRS, or NONE. The following is an example:

Joesunit 17:24:55 08/04/93

NET Alarms: LOS AIS ERRS

DTE Alarms: LOS Port 1

The user-programmable Element ID string is transmitted first to allow the COA
function to send a message with a specific meaning to some host (such as a log-on
message).

The identifier ERRS represents an alarm caused by ES, SES, and BPV errors.

COA Connection (SUPV)

This field controls the remote alarm reporting. ASCII alarm reporting through the
supervisory port is independent of TRAP alarm reporting. The ASCII alarm report
type is set by the following choices:

DISABLED.

Alarm reporting is disabled.

DIAL.

Sends reports through an attached AT command set compatible modem

connected to the SUPV serial port, which must dial out to a remote modem. The
message format is described in the Element ID field.

DIRECT.

Sends reports to a printer or terminal connected directly to the

supervisory port.

Primary Dial String and Secondary Dial String

These fields are ASCII strings for the primary and secondary call on alarm phone
numbers used in the DIAL mode. The strings must not include the ATDT
command prefix.

The unit makes three attempts to connect using the primary number. If all three
attempts fail, the unit makes three attempts to connect using the secondary number
(if it is not blank). If the secondary number fails, the unit waits five minutes and
then attempts to communicate using the primary number again. When a connection
is detected, the unit outputs the notification message and disconnects.

Initialization String

The modem initialization string is entered in this field. Refer to the modem’s
documentation for further information. The default setting is ATEQ0V1.

Disconnect String

This field identifies the character string to be output when the modem session is
terminated. The default setting is ATH.