Oxymitter 4000, Alarms o2 t/c shorted, Instruction manual – Emerson Process Management OXYMITTER 4000 IM-106-340 User Manual

Page 100

Advertising
background image

8-8

Instruction Manual

IM-106-340, Rev. 4.0

May 2006

Oxymitter 4000

Figure 8-4. Fault 2, Shorted Thermocouple

Fault 2, Shorted Thermocouple

Figure 8-4 shows the electronic assembly for an
Oxymitter 4000 with a membrane keypad (upper
view) and an Oxymitter 4000 with an LOI (lower
view). The upper view also shows J1 and test
points TP1 through TP6, located on the
microprocessor board, below the membrane
keypad or the LOI module.

Membrane Keypad

When Fault 2 is detected, the HEATER T/C LED
flashes twice, pauses for three seconds, and
repeats.

1. Using a multimeter, measure the voltage

from TP3+ to TP4-. If the reading is 0 ±0.5
mV, then a shorted thermocouple is likely.

2. Remove power and disconnect J1.
3. Measure the resistance from TP3+ to TP4-.

The reading should be approximately 20K
ohms.

4. If so, the short is not on the PC board. The

thermocouple wiring or the thermocouple is
shorted. See "Heater Strut Replacement" in
Section 9: Maintenance and Service.

LOI

When Fault 2 is detected, the LOI displays the
"O2 T/C Shorted" message.

1. Remove power. Unscrew and remove the

LOI module from the electronic assembly.

2. Reconnect power to the Oxymitter 4000.
3. Perform the diagnostic steps 1 through 4

shown for the membrane keypad.

37260020

LOI

KEYPAD

Alarms

O2 T/C Shorted

DIAGNOSTIC

ALARMS

TEST

POINTS

HEATER T/C

HEATER

O2 CELL

CALIBRATION

CALIBRATION RECOMMENDED

O2 CELL mV +

O2 CELL mv -

HEATER T/C +

HEATER T/C -

INC

INC

DEC

DEC

HIGH

GAS

LOW

GAS

CAL

TEST GAS +

PROCESS -

% O2

SW2

TP1

J1

TP2

TP3

RED

YEL

GRN

ORG

TP4

TP5

TP6

ON

Advertising