Figure 4-1. Electronics Housing

Terminals with LOI

Oxymitter 4000
Configuration

Located on the microprocessor board are two switches that configure outputs
(Figure 4-2). To access these switches, the LOI module must be removed.
SW1 determines if the 4-20 mA signal is internally or externally powered.
SW2 determines:

1. Range control, HART or LOCAL.
2. Oxygen range, 0 to 10% O

2

or 0 to 25% O

2

. (0 to 40% O

2

is also

configurable only through HART/AMS.)

3. The 4-20 mA signal, at fault or power up, 3.5 mA or 21.6 mA.

SW1 Setting

The two settings are internally or externally powering the 4-20 mA signal. The
factory setting is for the 4-20 mA signal to be internally powered.

3726001

1

AC L1

AC N

+

+

-

-

4-20

500 VA

SERIAL NO.
TAG NO.

OXYMITTER 4000

WATTS:

VOLTS:

FUSE:

LINE

OUTPUT:

Rosemount Analytical Inc.
Orrville, OH 44667-0901

85-264 VAC 48-62 Hz

TM

800-433-6076

4-20 mA

R

5 Amps

TM

HART

SMART FAMILY

4-20 mA
Signal

Logic I/O

Ground Lugs

Terminal
Block

Oxymitter 4000
Electronics
Housing

LOI

Remove power before changing defaults. If defaults are changed under power, damage to
the electronics package may occur.