Figure 2-8, Oxymitter 4000, Instruction manual – Emerson Process Management OXYMITTER 4000 IM-106-340 User Manual

Page 48

Advertising
background image

Oxymitter 4000

2-10

Instruction Manual

IM-106-340, Rev. 4.0

May 2006

Figure 2-8. Installation with Drip

Loop and Insulation Removal

ELECTRICAL
INSTALLATION (WITH
INTEGRAL
ELECTRONICS)

For Oxymitter 4000 with Integral Electronics

All wiring must conform to local and national codes.

P

S

U

E

I

T

P

I

C

R

H

W

E

N

T

H

G

C

KE

N

I

-

E

E

R

W

A

V I

S

O

L

P

-

X

O

M

T

A

G

NI

N

-

R

I

T

L

A

I

VE

-

E

E

H

GAS

CAL.

Drip
Loop

Logic I/O,
4-20 mA Signal

Line

Voltage

Replace Insulation

after Installing

Oxymitter 4000

Insulation

Adapter

Plate

Stack or Duct
Metal Wall

29340005

Disconnect and lock out power before connecting the power supply.

Install all protective covers and safety ground leads after installation. Failure to install covers
and ground leads could result in serious injury or death.

To meet the Safety Requirements of IEC 1010 (EC requirement), and ensure safe operation
of this equipment, connection to the main electrical power supply must be made through a
circuit breaker (min 10 A) which will disconnect all current-carrying conductors during a fault
situation. This circuit breaker should also include a mechanically operated isolating switch.
If not, then another external means of disconnecting the supply from the equipment should
be located close by. Circuit breakers or switches must comply with a recognized standard
such as IEC 947.

Advertising