Oxymitter 4000

Figure 8-5. Fault 3, Reversed Thermocouple

Fault 3, Reversed Thermocouple Wiring or
Faulty PC Board

Figure 8-5 shows the electronic assembly for an
Oxymitter 4000 with a membrane keypad (upper
view) and an Oxymitter 4000 with an LOI (lower
view). The upper view also shows J1 and test
points TP1 through TP6, located on the
microprocessor board, below the membrane
keypad or the LOI module.

Membrane Keypad

When Fault 3 is detected, the HEATER T/C LED
flashes three times, pauses for three seconds,
and repeats.

1. Using a multimeter, measure the voltage

from TP3+ to TP4-. If the reading is
negative, the thermocouple wiring is
reversed.

2. Check red and yellow wires in the J1

connector for the proper placement.

3. If the wiring is correct, the fault is in the PC

board. See "Electronic Assembly
Replacement" in
Section 9: Maintenance
and Service.

LOI

When Fault 3 is detected, the LOI displays the
"O2 T/C Reversed" message.

1. Remove power. Unscrew and remove the

LOI module from the electronic assembly.

2. Reconnect power to the Oxymitter 4000.
3. Perform the diagnostic steps 1 through 3

shown for the membrane keypad.

37260021

Alarms

O2 T/C Reversed

DIAGNOSTIC

ALARMS

TEST

POINTS

HEATER T/C

HEATER

O2 CELL

CALIBRATION

CALIBRATION RECOMMENDED

O2 CELL mV +

O2 CELL mv -

HEATER T/C +

HEATER T/C -

INC

INC

DEC

DEC

HIGH

GAS

LOW

GAS

CAL

TEST GAS +

PROCESS -

% O2

SW2

TP1

J1

TP2

TP3

RED

YEL

GRN

ORG

TP4

TP5

TP6

ON

LOI

KEYPAD

Advertising