5 Installation Procedure

YASKAWA ELECTRIC

SIEP C730600 69A 1000-Series Option SI-EP3 Technical Manual

17

7.

Use the second option modular connector CN1 port to daisy chain a series of drives where applicable.
Connection Diagram

Figure 8 Option Connection Diagram

Communication Cable Wiring

The option modular connector CN1 port 1 and port 2 act as a switch to allow for flexibility in cabling topology. For
example, a traditional star network topology may be employed by using a single port on the option. Alternatively,
a daisy-chained approach may be employed by using both option modular connector ports. This second
approach reduces the requirements of PROFINET switch ports.

Figure 8

Figure 9 Topology Options

<1> The ground wire provided in the option shipping package must be connected during

installation.

A1000

M

U/T1
V/T2

W/T3

R/L1
S/L2

T/L3

SI-EP3

PROFINET

Option

FE

PROFINET Master

PROFINET Cable

Motor

Power

PROFINET Cable

<1>

A1000

PLC

SWITCH

Yaskawa Drive

Yaskawa Drive

Yaskawa Drive

Yaskawa Drive

Yaskawa Drive

Yaskawa Drive

PLC

SWITCH

A1000