10 Troubleshooting

48

YASKAWA ELECTRIC SIEP C730600 69A 1000-Series Option SI-EP3 Technical Manual

Option Fault Monitors U6-98 and U6-99

The option can declare error/warning conditions via drive monitor parameters on the drive digital operator as shown in

Table 30

.

Table 30 Option Fault Monitor Descriptions

Two drive monitor parameters, U6-98 and U6-99 assist in network troubleshooting:

• U6-98 displays the first declared fault since the last power cycle. U6-98 is only cleared upon drive power-up.
• U6-99 displays the present option SI-EP3 status. U6-99 is cleared upon a network-issued fault reset and upon

power-up.

If another fault occurs while the original fault is still active, parameter U6-98 retains the original fault value and U6-99
stores the new fault status value.

Option Compatibility

A limited number of options may be simultaneously connected to the drive depending on the type of option. Refer to

Table 31

for more information. More details can be found in the Options and Peripheral Devices chapter of the drive

instruction manual.

Table 31 Option Card Installation

Fault Condition

Fault Declared

Status Value

(U6-98/U6-99)

Description

No Fault

N/A

0

No faults.

Force Fault

EF0

3

Network sent a message to force this node to the fault state.

Network Link Down

bUS

1300

No network link to option board.

Network Failure

bUS

1301

Connection with PLC Timeout.

Default MAC Address

None

1303

Factory default MAC Address programmed into the option. Return for
reprogramming.

No IP Address

None

1304

No IP Address has been programmed into the option.

No Station Name

None

1305

No Station Name has been programmed into the option.

Config Error

None

1306

Configuration error on power-up.

Init. Failure

None

1307

Initialize error on power-up.

Permanent

Communication Loss

bUS

1308

Fatal error in MAC/PHY hardware, requires power cycle to recover.

Option Card

<1> If two PG option cards are connected, use both CN5-B and CN5-C. If only one PG option card is connected to the drive, use the CN5-C

connector.

<2> These option cards are not available for the application with Motor 2 Selection.

<3> These option cards are not available with models CIMR-A4A0930 and 4A1200.

<4> When AI-A3 and DI-A3 are to be used as monitors, the card can be connected to any of CN5-A, CN5-B or CN5-C. The input status of AI-A3

can then be viewed using U1-21, U1-22, and U1-23, and the input status of DI-A3 can then be viewed using U1-17.

Connector

Number of Cards Possible

PG-B3, PG-X3

CN5-C

2

<1>

PG-RT3

<2> <3>

, PG-F3

<2> <3>

CN5-C

1

DO-A3, AO-A3

CN5-A, B, C

1

SI-C3, SI-EM3

<3>

, SI-EN3

<3>

, SI-ET3

<3>

,

SI-N3, SI-P3, SI-S3, SI-T3, SI-W3

<3>

, AI-

A3

<4>

, DI-A3

<4>

CN5-A

1