Option low priority alarm codes – Yaskawa SI-EP3 PROFINET Technical Manual User Manual

Page 37

Advertising
background image

8 Communication

YASKAWA ELECTRIC

SIEP C730600 69A 1000-Series Option SI-EP3 Technical Manual

37

Option Low Priority Alarm Codes

These codes are transmitted as Manufacturer Specific Diagnostic low priority alarms that can be seen in the PLC
configuration software. These low priority codes are the same codes that appear in the drive manual, except with an
offset of 0x1000.

Table 25 PROFINET Option Low Priority Alarm Codes

1025

Out of Control (CF)

• Check motor parameters
• Auto-tune

1027

External Fault 0 (EF0)

• Check PLC program
• Check MI switch setting
• Check option LEDs for fault indication

<1> Drive error code is stored in MEMOBUS/Modbus address 0080 Hex.

Drive Alarm

Code

(Hex)

<1>

<1> Drive error code is stored in MEMOBUS/Modbus address 0080 Hex.

Description

Drive Alarm

Code

(Hex)

<1>

Description

0401

Undervoltage (Uv)

0420

MEMOBUS/Modbus Test Mode Fault (SE)

0402

Overvoltage (ov)

0422

Motor Overheat (oH3)

0403

Heatsink Overheat (oH)

0427

PID Feedback Loss (FbL)

0404

Drive Overheat (oH2)

0428

PID Feedback Loss (FbH)

0405

Overtorque 1 (oL3)

042A

Drive Disabled (dnE)

0406

Overtorque 2 (oL4)

042B

PG Disconnected (PGo)

0407

Rum Command Input Error (EF)

0431

Option Watchdog Error (E5)

0408

Drive Baseblock (bb)

0432

Option Station Address Setting Error (AEr)

0409

External Fault 3, input terminal S3 (EF3) 0433

Option

Comm.

Cycle Setting Error (CyC)

040A

External Fault 3, input terminal S4 (EF4)

0434

High Current Alarm (HCA)

040B

External Fault 3, input terminal S5 (EF5)

0435

Cooling Fan Maintenance Time (LT-1)

040C

External Fault 3, input terminal S6 (EF6)

0436

Capacitor Maintenance Time (LT-2)

040D

External Fault 3, input terminal S7 (EF7)

0438

Option EEPROM Error (EEP)

040E

External Fault 3, input terminal S8 (EF8)

0439

External Fault (input terminal S1) (EF1)

040F

Cooling Fan Error (FAn)

043A

External Fault (input terminal S2) (EF2)

0410

Overspeed (oS)

043B

Safe Disable Input (HbbF)

0411

Excessive Speed Deviation (dEv)

043C

Safe Disable Input (Hbb)

0412

PG Disconnected (PGo)

043D

Mechanical Weakening Detection 1 (oL5)

0414

MEMOBUS/Modbus Comm. Error (CE)

043E

Mechanical Weakening Detection 2 (UL5)

0415

Option Communication Error (bUS)

043F

PLC Alarm (PA1)

0416

Serial Comm. Transmission Error (CALL)

0440

PLC Alarm (PA2)

0417

Motor Overload (oL1)

0441

Output Voltage Detection Fault (voF)

0418

Drive Overload (oL2)

0442

IGBT Maintenance Time (90%) (TrPC)

041A

Option Card External Fault (EF0)

0443

Soft Charge Bypass Relay Maintenance Time (LT-3)

041B

Motor Switch Command Input during Run (rUn)

0444

IGBT Maintenance Time (50%) (LT-4)

041D

Serial Comm. Transmission Error (CALL)

0445

Braking Transistor Overload (boL)

041E

Undertorque Detection 1 (UL3)

0448

Motor Overheat (NTC Input) (oH5)

041F

Undertorque Detection 2 (UL4)

0449

DriveWorksEZ Alarm (dWAL)

Drive Alarm

Code

(Hex)

<1>

Description

Corrective Action

PROFINET_E_conditional.book 37 ページ 2015年2月25日 水曜日 午後5時17分

Advertising