6 Related Drive Parameters

YASKAWA ELECTRIC

SIEP C730600 69A 1000-Series Option SI-EP3 Technical Manual

21

Table 7 Option Monitors

F7-34

(406)

<10>

Dynamic Input Assembly
Parameter 2

Sets configurable input 2.

Default: 0H
Min.: 0H
Max.: FFFFH

F7-35

(407)

<10>

Dynamic Input Assembly
Parameter 3

Sets configurable input 3.

Default: 0H
Min.: 0H
Max.: FFFFH

F7-36

(408)

<10>

Dynamic Input Assembly
Parameter 4

Sets configurable input 4.

Default: 0H
Min.: 0H
Max.: FFFFH

F7-37

(409)

<10>

Dynamic Input Assembly
Parameter 5

Sets configurable input 5.

Default: 0H
Min.: 0H
Max.: FFFFH

H5-11

(43C)

Communications ENTER Function
Selection

Select the function for the ENTER command that saves parameter data to
the drive.
0: Parameter changes are activated when ENTER command is written
1: Parameter changes are activated immediately without use of ENTER
command

Default: 1
Range: 0, 1

<1> To start and stop the drive with the option master device using serial communications, set b1-02 to 3. To control the drive frequency reference

via the master device, set b1-01 to 3.

<2> If F6-01 is set to 3 or 4, the drive will continue to operate when a fault is detected. Take safety measures, such as installing an emergency stop

switch.

<3> Available for software versions PRG: 1021 and later when using A1000. Refer to the instruction manual of a specific drive to determine if

settings 4 and 5 are available in the drive.

<4> Enabled in CLV, AOLV/PM, and CLV/PM control modes (A1-02 = 3, 6, or 7). When enabled, d5-01 determines whether the value is read as the

Torque Limit value (d5-01 = 0) or read as the Torque Reference value (d5-01 = 1). In CLV/PM, this value is read as the Torque Limit.

<5> The setting specifies that the Torque Reference or Torque Limit is to be provided via network communications (F6-06 = 1). The motor may

rotate if no torque reference or Torque Limit is supplied from the PLC.

<6> Cycle power for setting changes to take effect.

<7> If F7-13 is set to 0, then all IP Addresses (F7-01 to F7-04) must be unique.

<8> Set F7-01 to F7-12 when F7-13 is set to 0.

<9> Set F7-15 when F7-14 is set to 0 or 2.

<10> If a value other than 0 is assigned to parameters F7-23 to F7-27 and F7-33 to F7-37 by the drive, that value will take precedent over a value set

by the configuration software. If the value in the drive is 0 (default), the value from the configuration software is used.

No.

Name

Description

Value Range

U6-80 to U6-83

Online IP Address

SI-EP3 IP Address, U6-80 is the most significant octet.

0 to 255

U6-84 to U6-87

Online Subnet

Subnet, U6-94 is the most significant octet.

0 to 255

U6-88 to U6-91

Online Gateway

Gateway, U6-88 is the most significant octet.

0 to 255

U6-92

Online Speed

CN1 Port 1 Link Speed

10, 100

U6-93

Online Duplex

CN1 Port 1 Duplex Setting

0: Half, 1: Full

U6-94

Online Speed

CN1 Port 2 Link Speed

10, 100

U6-95

Online Duplex

CN1 Port 2 Duplex Setting

0: Half, 1: Full

U6-98

First Fault

First Option Board Fault

U6-99

Current Fault

Current Option Board Fault

No.

(Addr.

Hex)

Name

Description

Values